DR-120 Din rail power supply
120W Single Output Industrial DIN Rail Power Supply DR-120 series
Features:
Universal AC input / full range
Protections: Short circuit/ Over load/ Over voltage/ Over temperature
Cooling by free air convection
Can be installed on DIN rail TS-35/7.5 or 15
LED indicator for power on
100% full load burn-in test
Fixed switch frequency at 55KHz
2 years warranty
SPECIFICATIONS |
|||
OUTPUT |
|
||
Model |
DR-120-12 |
DR-120-24 |
DR-120-48 |
DC Voltage |
12V |
24V |
48V |
Rated Current |
10A |
5A |
2.5A |
Current Range |
0-10A |
0-5A |
0-2.5A |
Rated Power |
120W |
120W |
120W |
Ripple & Noise |
80mVp-p |
80mVp-p |
100mVp-p |
Voltage Adj. Range |
12-14V |
24-28V |
48-53V |
Voltage Tolerance |
±2% |
±1% |
±1% |
Line regulation |
±0.5% |
±0.5% |
±0.5% |
Load regulation |
±1% |
±1% |
±1% |
Setup, Rise Time |
500ms,70ms/230VAC 500ms,70ms/115VAC at full load |
||
Hold Up Time |
36ms/230VAC 32ms/115VAC at full load |
||
|
|
||
INPUT |
|
||
Voltage Range |
88~132VAC/176~264VAC selected by switch 47~63Hz; 248~370VDC |
||
AC Current |
2.6A/115VAC 1.6A/230VAC |
||
Efficiency |
80% |
84% |
85% |
Inrush Current |
Cold start 20A/115V 40A/230V |
||
Leakage Current |
<3.5mA/240VAC |
||
|
|
||
PROTECTION |
|
||
Over Load |
105%~150% rated output power |
||
Protection type: Constant current limiting, recovers automatically after fault condition is removed |
|||
Over Voltage |
15-16.5V |
29-33V |
58-65V |
Protection type: Shut down o/p voltage, re-power on to recover |
|||
Over Temp. |
85℃±5℃(TSW1) |
90℃±5℃(TSW1) |
90℃±5℃(TSW1) |
Protection type: Shut down o/p voltage, recovers automatically after temperature goes down |
|||
|
|
||
ENVIRONMENT |
|
||
Working Temp., Humidity |
-10℃~+60℃; 20%~90% RH non-condensing |
||
Storage Temp., Humidity |
-20℃~+85℃; 10%~95%RH |
||
Vibration |
10~500Hz, 2G 10min./1cycle, period for 60min, each along X, Y, Z axes |
||
|
|
||
SAFETY |
|
||
Withstand Voltage |
I/P-O/P: 3KVAC I/P-FG: 1.5KVAC O/P-FG: 0.5KVAC |
||
Isolation Resistance |
I/P-O/P, I/P-FG, O/P-FG: 100M Ohms / 500VDC/25℃/70%RH |
||
|
|
||
STANDARD |
|
||
Safety Standard |
Design refer to UL508,UL60950-1,TUV EN60950-1 |
||
EMC Standard |
Design refer to EN55011,EN55022,EN61000-3-2,-3,EN61000-4-2,3,4,5,6,8,11,EN55024,EN61000-6-2(EN50082-2), heavy industry level, criteria A |
||
|
|
||
OTHERS |
|
||
Dimension |
65.5*125.2*100mm(L*W*H) |
||
Weight |
0.79Kg |
||
Packing |
20pcs/carton/16.5kg/1.29CUFT |
||
|
|
||
NOTE |
|
||
1.All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature. 2. Ripple & noise are measured at 20MHz of bandwidth by using a 12” twisted pair-wire terminated with a 0.1μf & 47μf parallel capacitor. 3.Tolerance: includes set up tolerance, line regulation and load regulation. 4.The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives. |
110VAC/220VAC
50/60Hz