DR-60 Din rail power supply
60W Single Output Industrial DIN Rail Power Supply DR-60 series
Features:
Universal AC input/ full range
Protections: Short circuit/ Over load/ Over voltage
Cooling by free air convection
Can be installed on DIN rail TS-35/7.5 or 15
Isolation classⅡ
LED indicator for power on
100% full load burn-in test
2 years warranty
SPECIFICATIONS |
||||
OUTPUT |
|
|||
Model |
DR-60-5 |
DR-60-12 |
DR-60-15 |
DR-60-24 |
DC Voltage |
5V |
12V |
15V |
24V |
Rated Current |
6.5A |
4.5A |
4A |
2.5A |
Current Range |
0-6.5A |
0-4.5A |
0-4A |
0-2.5A |
Rated Power |
32.5W |
54W |
60W |
60W |
Ripple & Noise |
80mVp-p |
120mVp-p |
120mVp-p |
150mVp-p |
Voltage Adj. Range |
4.75-5.5V |
11.1-13.2V |
13.5-16.5V |
21.6-26.4V |
Voltage Tolerance |
±2% |
±1% |
±1% |
±1% |
Line regulation |
±1% |
±1% |
±1% |
±1% |
Load regulation |
±1% |
±1% |
±1% |
±1% |
Setup, Rise Time |
100ms,30ms/230VAC 200ms,30ms/115VAC at full load |
|||
Hold Up Time |
100ms/230VAC 23ms/115VAC at full load |
|||
INPUT |
|
|||
Voltage Range |
88~264VAC 47~63Hz; 124~370VDC |
|||
AC Current |
1.2A/115V 0.8A/ 230V |
|||
Efficiency |
76% |
82% |
83% |
84% |
Inrush Current |
Cold start 18A/115V 36A/230V |
|||
Leakage Current |
<1mA/240VAC |
|||
PROTECTION |
|
|||
Over Load |
105%~160% rated power |
|||
Protection type: Constant current limiting, recovers automatically after fault condition is removed |
||||
Over Voltage |
5.75-6.9V |
13.8-16.2V |
17.25-20.25V |
27.6-32.4V |
Protection type: Shut down o/p voltage, re-power on to recover |
||||
ENVIRONMENT |
|
|||
Working Temp., Humidity |
-20℃~+60℃; 20%~90% RH non-condensing |
|||
Storage Temp., Humidity |
-40℃~+85℃; 10%~95% RH |
|||
Temp. Coefficient |
±0.03%/℃(0~50℃) |
|||
Vibration |
10~500Hz, 2G 10min./1cycle, period for 60min, each along X, Y, Z axes |
|||
SAFETY |
|
|||
Withstand Voltage |
I/P-O/P: 3KVAC |
|||
Isolation Resistance |
I/P-O/P: 100M Ohms / 500VDC |
|||
STANDARD |
|
|||
Safety Standard |
Design refer to UL60950-1,TUV EN60950-1,EN50178 |
|||
EMC Standard |
Design refer to EN55011,EN55022,EN61000-3-2,-3,EN61000-4-2,3,4,5,6,8,11,EN55024,EN61000-6-2,EN61204-3, heavy industrial level, criteria A |
|||
OTHERS |
|
|||
Dimension |
78*93*56mm(W*H*D) |
|||
Weight |
0.3Kg |
|||
Packing |
48 pcs/carton/15.4KG/1.02CUFT |
|||
NOTE |
|
|||
1.All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature. 2.Ripple & noise are measured at 20MHz of bandwidth by using a 12” twisted pair-wire terminated with a 0.1μ & 47μ parallel capacitor. 3.Tolerance: includes set up tolerance, line regulation and load regulation. 4.The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives. |
88~264VAC47~63Hz; 124~370VDC
50/60Hz